Information on MWC units subject to 7.08(2) |
| |
Testing Frequency |
|
|
|
Facility name |
|
Ogden Martin of Haverhill |
Ogden Martin of Haverhill |
|
Facility address |
|
100 Recovery Way |
100 Recovery Way |
|
City |
|
Haverhill, MA 01835 |
Haverhill, MA 01835 |
|
DEP region |
|
NERO |
NERO |
|
FMF number |
|
132291 |
132291 |
|
SSEIS number |
|
121/7 |
121/7 |
|
Unit number |
|
1 |
2 |
|
Unit capacity; tons/day |
|
825 |
825 |
|
Unit design |
|
Mass burn waterwall |
Mass burn waterwall |
|
particulate matter control device (PMCD) |
|
FF |
FF |
|
other controls |
|
SDA,SNCR,CI |
SDA,SNCR,CI |
|
Pollutant/Parameter Monitored And Units Of Standard/Averaging Time |
|
|
|
|
cadmium; mg/dscm @ 7%O2 |
9 month |
0.04 |
0.04 |
|
averaging time |
|
test method |
test method |
|
mercury; mg/dscm @ 7%O2 |
quarter or 9 month |
0.028, 0.065, 0.080 |
0.028, 0.065, 0.080 |
|
averaging time |
|
test method |
test method |
|
lead; mg/dscm @7% O2 |
9 month |
0.44 |
0.44 |
|
averaging time |
|
test method |
test method |
|
dioxin/furan; ng/dscm @ 7% O2 |
9 month or 27 month |
30 |
30 |
|
averaging time |
|
test method |
test method |
|
particulate matter; mg/dscm@7% O2 |
9 month |
27 |
27 |
|
averaging time |
|
test method |
test method |
|
sulfur dioxide (SO2); less stringent of limit or percent reduction |
9 month |
29ppmvd/75% |
29ppmvd/75% |
|
averaging time |
|
24 hour block geom avg |
24 hour block geom avg |
|
hydrogen chloride (HCl); less stringent of limit or % reduction |
9 month |
29ppmvd/95% |
29ppmvd/95% |
|
averaging time |
|
test method |
test method |
|
nitrogen oxides (NOx);ppmvd @ 7% O2 |
CEMS |
205 |
205 |
|
averaging time |
|
24 hour arithmetic average |
24 hour arithmetic average |
|
carbon monoxide (CO);ppmvd @ 7%O2 |
CEMS |
100 |
100 |
|
averaging time |
|
4 hour block arith avg |
4 hour block arith avg |
|
PMCD inlet temp; degrees F or C |
CMS |
inlet tempature during last dioxin test + 17C(30F) |
inlet tempature during last dioxin test + 17C(30F) |
|
averaging time |
|
test method |
test method |
|
unit load; pounds of steam per hr |
CMS |
110% of load during last dioxin test |
110% of load during last dioxin test |
|
averaging time |
|
4 hr block arith avg |
4 hr block arith avg |
|
carbon feedrate for mercury; pounds of carbon per hour |
quarterly or 9 month |
greater than or equal to approved rate from mercury optimization testing |
greater than or equal to approved rate from mercury optimization testing |
|
averaging time |
|
test method |
test method |
|
carbon feedrate for dioxin/furan; pounds of carbon per hour |
9 month or 27 month |
greater than or equal to approved rate from mercury optimization testing |
greater than or equal to approved rate from mercury optimization testing |
|
averaging time |
|
test method |
test method |
|
carbon feedrate parameter; determined by applicant |
CMS |
greater than or equal to measured value during last mercury compliance test AND last dioxin compliance test |
greater than or equal to measured value during last mercury compliance test AND last dioxin compliance test |
|
averaging time |
|
determined later |
determined later |
|
opacity; percent |
9 month |
10% |
10% |
|
averaging time |
|
test method |
test method |
|
opacity; percent |
COMS |
10% |
10% |
|
averaging time |
|
6 minutes |
6 minutes |
|
fugitive ash; percent of time |
9 months |
5% of time |
5% of time |
|
averaging time |
|
test method |
test method |