Information on MWC units subject to 7.08(2)
 

Testing Frequency

  

Facility name

 

Ogden Martin of Haverhill

Ogden Martin of Haverhill

Facility address

 

100 Recovery Way

100 Recovery Way

City

 

Haverhill, MA 01835

Haverhill, MA 01835

DEP region

 

NERO

NERO

FMF number

 

132291

132291

SSEIS number

 

121/7

121/7

Unit number

 

1

2

Unit capacity; tons/day

 

825

825

Unit design

 

Mass burn waterwall

Mass burn waterwall

particulate matter control device (PMCD)

 

FF

FF

other controls

 

SDA,SNCR,CI

SDA,SNCR,CI

Pollutant/Parameter Monitored And Units Of Standard/Averaging Time

 

  

cadmium; mg/dscm @ 7%O2

9 month

0.04

0.04

averaging time

 

test method

test method

mercury; mg/dscm @ 7%O2

quarter or 9 month

0.028, 0.065, 0.080

0.028, 0.065, 0.080

averaging time

 

test method

test method

lead; mg/dscm @7% O2

9 month

0.44

0.44

averaging time

 

test method

test method

dioxin/furan; ng/dscm @ 7% O2

9 month or 27 month

30

30

averaging time

 

test method

test method

particulate matter; mg/dscm@7% O2

9 month

27

27

averaging time

 

test method

test method

sulfur dioxide (SO2); less stringent of limit or percent reduction

9 month

29ppmvd/75%

29ppmvd/75%

averaging time

 

24 hour block geom avg

24 hour block geom avg

hydrogen chloride (HCl); less stringent of limit or % reduction

9 month

29ppmvd/95%

29ppmvd/95%

averaging time

 

test method

test method

nitrogen oxides (NOx);ppmvd @ 7% O2

CEMS

205

205

averaging time

 

24 hour arithmetic average

24 hour arithmetic average

carbon monoxide (CO);ppmvd @ 7%O2

CEMS

100

100

averaging time

 

4 hour block arith avg

4 hour block arith avg

PMCD inlet temp; degrees F or C

CMS

inlet temperature during last dioxin test + 17C(30F)

inlet temperature during last dioxin test + 17C(30F)

averaging time

 

test method

test method

unit load; pounds of steam per hr

CMS

110% of load during last dioxin test

110% of load during last dioxin test

averaging time

 

4 hr block arith avg

4 hr block arith avg

carbon feed rate for mercury; pounds of carbon per hour

quarterly or 9 month

greater than or equal to approved rate from mercury optimization testing

greater than or equal to approved rate from mercury optimization testing

averaging time

 

test method

test method

carbon feed rate for dioxin/furan; pounds of carbon per hour

9 month or 27 month

greater than or equal to approved rate from mercury optimization testing

greater than or equal to approved rate from mercury optimization testing

averaging time

 

test method

test method

carbon feed rate parameter; determined by applicant

CMS

greater than or equal to measured value during last mercury compliance test AND last dioxin compliance test

greater than or equal to measured value during last mercury compliance test AND last dioxin compliance test

averaging time

 

determined later

determined later

opacity; percent

9 month

10%

10%

averaging time

 

test method

test method

opacity; percent

COMS

10%

10%

averaging time

 

6 minutes

6 minutes

fugitive ash; percent of time

9 months

5% of time

5% of time

averaging time

 

test method

test method