- This page, BBRS Fire Prevention and Fire Protection Advisory Committee Meeting - 7.22.26, is offered by
- Division of Occupational Licensure
- Office of Public Safety and Inspections
- Board of Building Regulations and Standards
Public Meeting Notice BBRS Fire Prevention and Fire Protection Advisory Committee Meeting - 7.22.26
Overview
This is a remote meeting. You can participate from your computer, laptop, or smartphone. See Meeting Agenda for details.
You will need
Microsoft Teams meeting link and dial-in number
Meeting ID: 278 001 192 490 0
Passcode: 4uG6VP9x
Dial in by phone
+1 857-327-9245,,207296447# United States, Boston
Phone conference ID: 207 296 447#
In accordance with the provisions of G.L. c. 30A § 20, notice is hereby given that the Board of Building Regulations and Standards 11th Edition Fire Prevention and Fire Protection Subcommittee will be convening a meeting.
If you need reasonable accommodation to participate in the meeting, please reach out to Cheryl Yebba at 617- 701-8711. The Agency will make best efforts to accommodate requests received in a timely manner.
Meeting Minutes
Meeting Minutes – BBRS Fire Prevention and Fire Protection Committee
In accordance with the provisions of G.L. c. 30A § 20, the Board of Building Regulations and Standards Fire Prevention and Fire Protection Subcommittee convened a regular meeting on:
Microsoft Teams Meeting July 22, 2026
The topics shown below were discussed at the aforementioned meeting: 9:34 AM Chair David LeBlanc called the open meeting to order.
Informational note: All votes were taken by roll call. Where each member voted in favor, the vote will be reported as unanimous.
Subcommittee members present
- David LeBlanc
- Matthew Bourque
- Tom Farland
- Carissa Lisee
- Luke McKneally
- Steven Nocco
- Jake Nunnemacher
Subcommittee members absent
- Eric Svahn
DOL Staff Present
- Tammy Gropman, Executive Director
- Charles Kilb, Senior Board Counsel
- Andrew Chase, Associate Executive Director
Acknowledged Public Attendees
- none
- Reviewed, Discussed, and Voted Minutes
- Carissa Lisee motioned to approve meeting minutes for June 10,2026, seconded by Matthew Bourque. A roll call vote was held, none opposed, none abstained. Motion passed unanimously.
- Reviewed and Discussed Code change tracker form
- Members briefly reviewed the status of the code change tracker. It was noted that the prior meeting focused primarily on Section 907 and that two previously approved amendments required additional revision to address technical and legal concerns. Members indicated that the updated information from the current discussion would be added to the tracker as needed.
- Reviewed, Discussed, and Voted Assigned code sections with track changes
- Chapter 9 IBC 2024
- Members reviewed revised language for Section 907.2.6, Exception 2, applicable to Group I occupancies. The discussion focused on the documentation required when private-mode signaling is used and whether the building official should receive fire prevention, fire suppression and emergency evacuation plan or an emergency action plan approved by the fire official. Members reviewed the terminology and requirements of 527 CMR 1.00, including Chapter 10, Section 10.8 and Section 10.8.2.1, and distinguished those provisions from the construction-related planning requirements of 527 CMR 1.00 Chapter 16. Members revised the amendment to refer to the “Emergency Action Plan” under 527 CMR 1.00 Chapter 10 and clarified the relationship between private-mode signaling installed in accordance with NFPA 72 and staff evacuation responsibilities. The revised paragraph replaced the language approved at the previous meeting. Jake Nunnemacher motioned to approve language, seconded by Tom Farland. The committee voted to approve Section 907.2.6, Exception 2, as amended. A roll call vote was held, none opposed, none abstained. Motion passed unanimously.
- Members reviewed revised language for Section 907.5.2.2.6 concerning private-mode audible signaling. Consistent with the changes made to Section 907.2.6, members replaced references to a fire prevention, fire suppression and emergency evacuation plan with a reference to the Emergency Action Plan under 527 CMR 1.00 Chapter 10. Members also discussed whether “emergency action plan” should be capitalized or treated as a defined term and determined that no further change was necessary. Jake Nunnemacher motioned to approve language, seconded by Tom Farland The committee voted to approve Section 907.5.2.2.6 as amended, completing the committee’s review of Section 907. A roll call vote was held, none opposed, none abstained. Motion passed unanimously
- Members reviewed Section 908 concerning emergency alarm systems. Jake Nunnemacher motioned to discuss and approve section 908, seconded by Matt Bourque. Subcommittee discussed adding a signpost to the applicable hazardous-material provisions of 527 CMR 1.00. The committee voted to approve Section 908 as amended. A roll call vote was held, none opposed, none abstained. Tom Farland was absent for this vote. Motion passed unanimously.
- Members reviewed Section 915 concerning carbon monoxide detection. Jake Nunnemacher motioned to approve section 915, seconded by Carissa Lisee. For the exception to Section 915.1, members discussed whether the phrase “not normally occupied” should be retained for factory, storage and utility occupancies. Concerns were raised that “normally occupied” could create uncertainty regarding facilities occupied only during certain hours. The proposed amendment removed “normally” so the exception would apply to spaces that are not occupied.
- Members reviewed Section 915.2.4 and discussed carrying forward the 10th Edition requirement that an area containing carbon monoxide-producing forced-air equipment receive occupant notification. Members also supported referring to both carbon monoxide detector signals and carbon monoxide alarm signals to distinguish system detectors from standalone alarms.
- Chapter 9 IBC 2024
- Members reviewed Sections 915.2.6 through 915.2.8. The amendments carried forward existing Massachusetts provisions, replaced the former reference to 248 CMR with an updated signpost, and retained technical options recognized by the fire code for existing buildings. Members also discussed deleting an allowance that permitted the fire code official to approve standalone carbon monoxide alarms where no fire alarm system was installed. Concerns were raised that battery-operated or plug-in alarms may not be consistently tested, maintained or retained in service.
- Members reviewed new Section 915.4.3, requiring combination smoke and carbon monoxide alarms to use a simulated voice-and-tone feature that clearly distinguishes between smoke and carbon monoxide activations. Members discussed the differences between the temporal-three smoke signal and temporal-four carbon monoxide signal, the limited likelihood that occupants would recognize the signals without a voice message, and the availability and cost of compliant combination devices. Members confirmed that the requirement applies to combination alarms complying with UL 217 and UL 2034 and does not prohibit the use of separate smoke and carbon monoxide devices.
- Members reviewed Section 915.4.4 and supported carrying forward the requirement that carbon monoxide alarms within an affected area be interconnected so activation of one device provides notification throughout that area, rather than throughout the entire building.
- Members reviewed Section 915.5.3 concerning combination smoke and carbon monoxide system detectors. Members discussed requiring a simulated voice-and-tone feature or, alternatively, permitting a control unit or annunciator within the space to provide a clear alphanumeric indication distinguishing a fire alarm from a carbon monoxide alarm. Members considered the clarity and enforceability of the proposed wording and retained the language as submitted.
- Members reviewed Sections 915.5.4 through 915.5.6, including deletion of an exception concerning occupant notification, requirements for carbon monoxide duct detectors, and inspection, testing and maintenance provisions. A roll call vote was held, none opposed, none abstained. Motion passed unanimously. The committee voted to approve Section 915 as amended.
- Members reviewed Section 916 concerning gas detection systems. For Section 916.11, members discussed inspection, testing, calibration and sensor replacement. Rather than specifying testing at intervals of not less than annually, members supported language requiring compliance with the applicable NFPA standards and manufacturer recommendations because the necessary frequency may vary by system, sensor and process.
- Members discussed permitting and fire-code references for gas detection systems associated with hazardous materials and industrial processes. Members noted that gas detection may be required for hazardous materials or may be incorporated into a process independently of a building-code requirement. For Section 916.2.1, concerning toxic and highly toxic gases, members reviewed 527 CMR 1.00 Chapters 60 and 68. Because Chapter 68 directs users to Chapter 60, the proposed signpost was revised to reference 527 CMR 1.00 Chapter 68 without separately listing Chapter 60. Jake Nunnemacher motioned to approve, Seconded by Steven Nocco. A roll call vote was held, none opposed, none abstained. Motion passed unanimously. The committee voted to approve Section 916 as amended.
- Members reviewed Section 906 concerning portable fire extinguishers. In Section 906.1, members replaced the reference to the International Fire Code with a reference to Chapter 33 for extinguisher requirements during construction. For Section 906.4, concerning cooking-equipment fires, members removed multiple IFC references and added a signpost to 527 CMR 1.00 Chapter 13. Members also reviewed Sections 906.4.1 and 906.4.2 concerning extinguishers for solid-fuel cooking appliances and deep-fat fryers and retained the requirements carried forward from the 10th Edition. Jake Nunnemacher motioned to approve, seconded by Steven Nocco. A roll call vote was held, none opposed, none abstained. Motion passed unanimously. The committee voted to approve Section 906 as amended.
- Members began reviewing Section 918 concerning emergency responder communication enhancement systems. Jake Nunnemacher motioned to approve, seconded by Tom Farland. The chair then commenced a complete review of the Section.
- Members discussed adding NFPA 1225, 2022 edition, to Chapter 35 and adding a definition of “agency.” It was explained that the existing IBC provision consists primarily of a reference to IFC Section 510, while the proposed amendment would bring the detailed IFC technical requirements into 780 CMR, consistent with the approach taken in prior Massachusetts editions.
- Members discussed whether the opening reference should apply only to “new buildings.” Concerns were raised that retaining “new” could prevent the requirements from applying when Chapter 34 directs an existing building back to Section 918. Members reviewed 2024 IEBC Section 908, which requires evaluation of emergency responder communication coverage during certain Level 3 alterations and may require an existing building to be provided with compliant coverage. Members discussed whether Section 918 should instead reference Chapter 34 for existing buildings. Members discussed the respective responsibilities of the building official, fire official, frequency license holder, frequency licensing authority and other radio-system authorities. Concerns were raised that the technical requirements include numerous decisions involving radio frequencies, FCC licenses and operational needs that may be outside the building official’s expertise or authority. Members also noted that the installed equipment remains a building system involving permitting, fire-resistance, monitoring and integration with the fire alarm system and therefore includes responsibilities within the building official’s jurisdiction. Members discussed whether the amendment should retain detailed IFC Section 510 provisions, refer users directly to IFC Section 510, or revise the detailed provisions to distinguish the determinations and approvals assigned to each authority. Members considered the experience under the 10th Edition language. Some members reported that the existing detailed provisions had not caused difficulties and were useful to building officials, fire departments and design professionals. Others supported leaving the technical requirements in the fire code and using a signpost from the building code. Members also discussed language requiring consultation between building and fire officials but raised concerns that consultation alone would leave the final decision with the building official even where a determination involves a protected FCC license or the operational requirements of another agency. Legal counsel noted that the language can defer to non-building officials so long as those officials actually have legal authority, he indicated to be consistent appropriate citations are needed when that deferral is made. Members further noted that the IFC contains an exception for buildings under 12,000 square feet and raised concerns about communication coverage in smaller, potentially unsprinklered buildings. No vote was taken on Section 918. Members determined that additional work was required to identify the authorities supporting each fire-code and federal licensing reference and to revise the language so the responsibilities of the building official, fire official and applicable frequency authorities are clearly separated. Review of Sections 903 and 918 remained outstanding.
b. Chapter 1, 2024 IBC
- No substantive Chapter 1 amendments were reviewed under this agenda item. Members requested that a future meeting include an update regarding the BBRS’s consideration of previously submitted Chapter 1 and Chapter 33 proposals.
- Reviewed, Discussed, and Voted Front-End Amendments and Code Change Proposals
- Chapter 4, 11th Edition 780 CMR – Members received an update on the Chapter 4 front-end amendment document, which was reported to be approximately three-quarters complete. The completed draft is to be distributed for committee review before a future vote.
- Members also identified a potential omission concerning high-piled combustible commodities and high-piled high-hazard commodities in merchandising and retail occupancies. Members noted that the 9th Edition included definitions addressing conditions such as six-foot-high storage of Group A plastics in large retail buildings, while comparable language was not carried into the 10th Edition. Members discussed developing language for the 11th Edition to address these conditions in large retail and big-box occupancies that may not otherwise qualify as conventional high-piled rack storage.
- Reviewed and Discussed Homework Assignments
- Members discussed completing the remaining Chapter 9 work. Additional revisions will be prepared for Section 918 to distinguish building-code, fire-code and frequency-licensing responsibilities while retaining the necessary technical requirements. Work will also continue on Section 903, including review of a table carried forward from the prior edition. The revised Sections 903 and 918 are to be circulated before the next meeting when possible.
- Members also discussed completing the Chapter 4 front-end amendment document and preparing proposed language addressing high-piled combustible and high-hazard commodities in merchandising and retail occupancies.
- Reviewed Future Meeting Dates
- Members confirmed that the next meeting would be held on August 7, 2026, followed by the previously scheduled August 19, 2026, meeting. Members also discussed adding meetings on September 9, September 23, October 14 and October 28, 2026, to allow sufficient time to complete the 11th Edition review. The additional dates will be distributed for members to place on their calendars.
- Discussed Matters Not Reasonably Anticipated 48 Hours in Advance of the Meeting
- Members requested that the next meeting include a discussion of the BBRS’s disposition of the committee’s Chapter 1 and Chapter 33 proposals. No substantive discussion of those actions occurred during this meeting.
- Adjournment – The next meeting is scheduled for August 7, 2026, at 1 PM.
- Jake Nunnemacher motioned to adjourn, seconded by Eric Svahn. A roll call vote was held, none opposed, none abstained. Motion passed unanimously.
- The meeting adjourned at 12:33 PM.
Items Relied Upon During Open Meeting
- Agenda
- Meeting Minutes
- Code Change Proposals
- 2024 IRC
- 2024 IBC
- Related 780 CMR provisions
Agenda
| Member |
|---|
| David LeBlanc |
| Matthew Bourque |
| Tom Farland |
| Carissa Lisee |
| Luke McKneally |
| Steven Nocco |
| Jake Nunnemacher |
| Eric Svahn |
It is anticipated that the topics shown below will be discussed at the aforementioned meeting:
- Review/Discuss/Vote Minutes of the following FPFP meetings:
- June 10, 2026
- Review/Discuss Code change tracker form
- Review/Discuss/Vote Assigned code sections with track changes
- Chapter 9 IBC 2024
- Chapter 1 IBC 2024
- Review/Discuss/Vote Front end amendments and code change proposals
- Chapter 4 11th Edition 780 CMR
- Review/Discuss Homework assignments
- Review Future Meeting Dates
- Discuss matters not reasonably anticipated by the chair, 48 hours in advance of the meeting