- This page, Board of Elevator Regulations Meeting - 4.28.26, is offered by
- Division of Occupational Licensure
- Office of Public Safety and Inspections
Public Meeting Notice Board of Elevator Regulations Meeting - 4.28.26
Overview
This meeting will be held both in person and VIRTUALLY. See the details in the agenda.
You will need
The meeting can be accessed remotely via the link and dial-in information below:
Microsoft Teams meeting link and dial-in number
Join: Microsoft Teams Meeting Link
Meeting ID: 231 601 865 537 518
Passcode: n5kE3p5S
Dial in by phone
+1 857-327-9245,,548606251# United States, Boston
Phone conference ID: 548 606 251#
In accordance with the provisions of G. L. c. 30A, §20, and Chapter 2 of the Acts of 2025, notice is hereby given that a hybrid meeting of the Board of Elevator Regulations will be held on Tuesday, April 28, 2026, at 1:00 p.m.
Meeting Minutes
In accordance with the provisions of G. L. c. 30A, §20, and Chapter 2 of the Acts of 2025, notice is hereby given that a hybrid meeting of the Board of Elevator Regulations convened on Tuesday, April 28, 2026, at 1:00 p.m.
Call to Order
The meeting was called to order at 1:05 PM by Chair David Gaudet and announced that the session would be recorded.
Roll Call / Attendance
Board Members Present – In person/Remote
- David Gaudet – Building Owners - Chair
- Christopher Towski – Fire Services
- Pat Sampson – Licensed Elevator Mechanic
- Brian Ronan – Boston Inspectional Services
- Anthony Buonopane – Chief of Elevator Inspections
- Neil Mullane – Elevator Manufacturers
- William Pugliese – Building Inspector Outside of Boston
Board Member Absent
David McGuire – Insurance Company Representative
DOL Staff Present – In person
- Peter Kelley – Board Counsel
- Gaylee Richardson – Assistant to the Chief of Elevator Inspections
- Jay Ryan – Assistant Chief of Elevator Inspections
- John Rubyck – Code Coordinator
- Walter Zalenski – Supervisor of Elevator Inspectional Services
Guests – In person/Remote
- Joseph Morrissey
- Colby Bruce
- Galina Slezinger
- Doug Anderson
The topics shown below were discussed at the aforementioned meeting
- Chris Towski made a motion to move to a closed session pursuant to G. L. c. 30A, § 18, ¶ 5(d), for the purpose of conducting an adjudicatory conference in the matter of VAR25-0085 and VAR25-0086, and the motion was seconded by Brian Ronan.
- The motion passed by roll call vote. Vote 7-0-0
- During closed session, the Board took the following action: provided additional direction to the variance petitioner.
- A motion was made by Neil Mullane to exit closed session and enter open session which was seconded by Chris Towski.
- The motion passed by roll call vote. Vote 7-0-0
- VAR25-0004 (Exhibit 1)
57 Union Street Newton
State ID: 207-W-20484
Code Reference: ASME A18.1 2014 section 3.1.2.2
Petitioner: Galina Slezinger
The petitioner is back before the board after being in front of the board on February 3, 2026, when the board voted to place the item on hold for no more than 60 days, which was a deadline of April 4, 2026, for the petitioner to provide documentation to address the attendant operation and controls with Architectural Access Board (AAB) and all applicable codes. The petitioner provided a memo dated April 3, 2026, addressed to the Board of Elevator Regulations.
The petitioner was previously before board on December 2, 2025, August 26, 2025, June 3, 2025, and March 4, 2025, seeking a variance from ASME A18.1 2014 section 3.1.2.2 for overhead clearance to install new lift to replace the existing lift. The board had requested documentation to support the low overhead including structural drawings and to present a solution to meet safety.
Doug Anderson stated the AAB approval requires that the lift will not be controlled by the rider and that only a staff member can control the lift.
Neil Mullane moved to grant the variance for the low overhead conditions. After an exhaustive review of the feasibility of code compliance, the petitioner has proven hardship for existing conditions and has proposed safety modifications, as follows. Riders must be seated in the downward direction, signage will be added, audio/visual alerts, remote pendant operation must ensure the lift is only operated in the physical presence of an attendant, and, with the exception of a stop switch, no controls in the unit. The motion was seconded by Anthony Buonopane. The motion passed by unanimous roll call vote. Vote 7-0-0
- VAR26-0024 (Exhibit 2)
68 Beacon Street Boston
State ID: 1-P-702
Code Reference: 524 CMR 35.00 – Section 2.8.3
Petitioner: Joseph Morrissey
The petitioner is seeking a variance from 524 CMR 35.00 – Section 2.8.3 regarding pipes in the hoistway.
Joseph Morrissey summarized the request indicating the drum machine was installed in 1917. Otherwise, they would follow the requirements in 8.7 for alterations. The existing elevator floor will be lowered for better access to the door with an engineer to review the floor. Anthony Buonopane read from ELV-2 and indicated oil and pipe lines installed prior to 1950 are grandfathered in.
David Gaudet moved to deny the variance because the petitioner’s testimony demonstrates that the elevator is compliant. The motion was seconded by Chris Towski. The motion passed by unanimous roll call vote. Vote 7-0-0
- Processing of variance decisions. As set forth in the meeting notice, board was advised as to those administratively processed variances.
- Processing of variance withdrawal requests. As set forth in the meeting notice, board was advised as to those processed withdrawals.
- Chris Towski moved to adjourn at 2:51 PM and the motion was seconded by Brian Ronan. Motion passed by unanimous vote. Vote 7-0-0
Exhibit List
Exhibit 1: Variance packet for 57 Union Street Newton
Exhibit 2: Variance packet for 68 Beacon Street Boston
Agenda
It is anticipated that the topics shown below will be discussed at the aforementioned meeting:
- Roll Call.
- Closed Session, closed pursuant to G. L. c. 30A, § 18, ¶ 5(d), for the purpose of conducting an adjudicatory conference in the matter of VAR25-0085 and VAR25-0086.
VAR25-0004&
57 Union Street, Newton
State ID: 207-W-20484
Code Reference: ASME A18.1 2014 section 3.1.2.2
Petitioner: Galina SlezingerThe petitioner is back before the board after being in front of the board on February 3, 2026, when the board voted to place the item on hold for no more than 60 days, which was a deadline of April 4, 2026, for the petitioner to provide documentation to address the attendant operation and controls with AAB and all applicable codes. The petitioner provided a memo dated April 3, 2026, addressed to the Board of Elevator Regulations.
The petitioner was before board on December 2, 2025, August 26, 2025, June 3, 2025, and March 4, 2025, seeking a variance from ASME A18.1 2014 section 3.1.2.2 for overhead clearance to install new lift to replace the existing lift. The board had requested documentation to support the low overhead including structural drawings and to present a solution to meet safety.
VAR26-0024
68 Beacon Street Boston
State ID: 1-P-702
Code Reference: 524 CMR 35.00 – Section 2.8.3
Petitioner: Joseph Morrissey< br />The petitioner is seeking a variance from 524 CMR 35.00 – Section 2.8.3 regarding pipes in the hoistway.
- Variance Administrative Decisions processed. VAR26-0020 and VAR26-0023 with State IDs 348-P-612 and 348-P-611 at the address of 26 Harvard Street Worcester. VAR26-0025 and VAR26-0026 with State IDs 348-P-1601 and 348-P-1602 at the address of 101 Plantation Street Worcester.
- Variance Withdrawal request processed. VAR26-0007, as a new installation, request for variance at the address of 245 Centre Street Boston, was requested to be withdrawn by the petitioner.
- Matters not reasonably anticipated 48 hours in advance of meeting.
- Old business (The Board may or may not discuss):
VAR25-0085 & VAR25-0086
40 Broadway Taunton
State IDs: 293-P-285 & 293-P-286
Code Reference: 524 CMR - A17.1 – 2013 Section 2.2.4.2
Petitioner: Thomas McCarthyThe petitioner was before the board on April 7, 2026, and the board voted to defer the case to a future Quasi-Judicial Closed Session for additional review.
The petitioner is back before the board after previously being before the board on January 27, 2026, when the board voted to place the item on a 60-day hold, which provided a deadline of March 28, 2026. The applicant was requested to gather more information including pit dimensions, plan view, equipment information and demonstration of hardship. New documentation submitted March 27, 2026, included two design drawings and a photograph.
The petitioner was seeking a safety-equivalent variance from 524 CMR - A17.1 – 2013 Section 2.2.4.2 regarding the ladder installation for units 293-P-285 and 293-P-286.
VAR26-0019
220 State Street Springfield
State ID: 281-P-691
Code Reference: 524 CMR 8.06
Petitioner: Christine ParnellThe petitioner was before the board on April 7, 2026, and the board voted to place the item on a 60-day hold, which provided a deadline of June 8, 2026, for the applicant to gather evidence proving the battery lower is not required by any other applicable codes.
The petitioner is seeking relief from 524 CMR 8.06 by requesting permission to remove the battery lowering unit from this elevator.
If you need reasonable accommodations to participate in the meeting, please reach out to Cheryl Yebba at 617-701-8711. While the Board will do its best to accommodate you, certain accommodations may not be available if requested immediately before the meeting.
Please be advised that recording meetings without prior permission from the board chair, by any means, including the use of any A.I. applications, is strictly prohibited.