In accordance with Massachusetts General Laws Chapter 30A, Section 20, notice is hereby given that a meeting of the 527 CMR 12 Massachusetts Electrical Code Interpretation Committee is scheduled for Tuesday, March 18, 2025 at 1:00 p.m. via Microsoft Teams Meeting.

Agenda

527 CMR 12.00

Massachusetts Electrical Code Interpretation Code Committee

Agenda, March 18, 2025

Date:             March 18, 2025

Time:             1:00 p.m.

Location:       Microsoft Teams Meeting

Please be advised that recording meetings, by any means, including the use of any A.I. applications, without prior permission is strictly prohibited.

Microsoft Teams Meeting

Join on your computer, mobile app or room device

Click here to join the meeting

Meeting ID: 228 177 731 347 
Passcode: cWCe5U

Download TeamsJoin on the web

Or call in (audio only)

+1 857-327-9245,,160763968#   United States, Boston

Phone Conference ID: 160 763 968#

Find a local numberReset PIN

  1. Call to Order
  2. Introductions
  3. Agenda items:
    1. Review Meeting Minutes from February 18, 2025.
    2. Requests for interpretation:
      1. 527 CMR 12.00, 110.26(C)(3) submitted by Walter “Ted” Dow received January 18, 2025.

        Response: Yes, 110.26(c)(3) is not applicable.

        The above response was not approved by the BFPR.  Question #2 is to be reviewed again by the Committee.

        Question #2 An electrical room contains multiple pieces of equipment, each rated less than 800 amperes.  The room additionally contains a 2,500-ampere bus duct riser, with multiple plug-in disconnects, each rated less than 800 amperes.  The room entrance/egress door is located within 25-feet of the nearest edge of the equipment working space.  As all equipment in the room is less than 800-amperes and the plug-in disconnects on the bus duct are each rated less than 800-amperes does 527 CMR 12, 110.26(c)(3) permit the entrance/egress door to swing into the room, without panic (fire exit hardware)?

                           ii.  527 CMR 12.00, 352 submitted by Silva Gustavo received January 30, 2025.

                                Question #1 Does NEC Article 352 require expansion fittings on a PVC riser mounted to a telephone pole?

                                   iii.  527 CMR 12.00, 215.18 submitted by Sarah Andrade received February 21, 2025.                     

                                        Question 1# Based on the New 2023 article 215.18, are surge protection devices required in each sub panel in the                                                     dwelling units?

                                 iv.  527 CMR 12.00, 100-110.26(a)(3) submitted by Kevin McKeown received February 26, 2025.   

                                       Question 1# Is Busway/busduct with multiple plug openings for disconnecting means/devices considered to be electrical                                        equipment according to the definition in article 100 Equipment?

                                       Question #2 If Busway/busduct is electrical equipment as article 100 states and is rated at 2500amps with 2-400amp                                              disconnects and is located in an electrical room would the personnel doors need to open in the direction of egress with                                          listed fire exit hardware.

  1. Items not anticipated    
  2. Adjournment